Home > Oil Appliances > Domestic Heating > Air Handler

Air Handlers and Make-Up Air Units

Aero's fan coil units can be used as air handlers for space heating or for fresh air make-up. For all the versatility and features you need, trust Aero.

-Three models: MP-25, MP-55, MP-75
- Dual purpose ­ space heating or fresh air make-up
- Casings are made with a highly efficient, variable speed, reverse impeller blower/motor combination with a rheostat (variable speed controller)
- MP-55 and MP-75 are suppled with 3-speed motors
- Our air handlers can be mounted in any position (multi positional)
- All the air handlers have an integral filter, and the air filter for the MP-25 is washable
- A plenum flange for the supply and return air is supplied for easy installation
- All air handlers are designed for easy installation and servicing


 

High-efficiency hot water coil

 

Specifications

MP-25
Coil Size 15-1/2"X14"X5-1/2" Pipe Connections: 3/4"
Casing Size 30"X14-3/8"X10" Weight: 37 lbs / 17 kgs
Blower CFM Range Variable 0-360 (rheostat supplied) Plenum Dimensions:
Supply: 12"X12"
Return: 12"X8"
Blower CFM Input 360  
Water Flow 5.25 gpm  

 Entry Air Temp. F 60 60 60 -30 -30 -30
Entry Water Temp. F 140 180 200 140 180 200
 Btu Output 25,000 38,572 45,394 54,193 67,414 74,045
Leaving Air
Temp. F
127 158 175 109 143 160

MP-55
 Coil Size  25-7/8"X18"X5-1/2"   Pipe Connections: 3/4"
 Casing Size  29-3/8"X26-1/2"X18"  Weight: 117 lbs / 53 kgs
 Blower CFM Range  690, 850, 920 (3-speed motor)  Plenum Dimensions:
Supply: 15"X21"
Return: 22-1/2"X14"
 Blower CFM Input  850  
 Water Flow  6.5 gpm  
 Entry Air Temp. F 60 60 60 -30 -30 -30
Entry Water Temp. F 140 180 200 140 180 200
 Btu Output 55,521 79,895 93,475 114,237 142,076 156,037
Leaving Air
Temp. F
121 146 163 95 125 140


MP-75
 Coil Size  25-7/8"X18"X5-1/2"   Pipe Connections: 3/4"
 Casing Size  30-7/8"X26-1/2"X20"  Weight: 122 lbs / 55 kgs
 Blower CFM Range  1250,1350, 1500 (3-speed motor)  Plenum Dimensions:
Supply: 15"X21"
Return: 22-1/2"X16"
 Blower CFM Input  1500  
 Water Flow  7.0 gpm  
 Entry Air Temp. F 60 60 60 -30 -30 -30
Entry Water Temp. F 140 180 200 140 180 200
 Btu Output 75,000 110,809 134,899 162,485 202,812 223,073
Leaving Air
Temp. F
109 127 143 70 95 108